| 47175.1 |
SS200-16 Roof Panel |
SS200-16 Roof Panel, 16" Wide X 24 ga Steel attached to Steel Purlins at 6' Spacing |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +NA/-31.2 PSF Other: Per ASTM E1592 Test over 16 ga Supports located at 6' on centers With Safety Factor of 2.0. Materials and Installation shall be per Sections 1506 And 1507.4 of the 2023 FBC Building Code. |
Installation Instructions FL47175_R0_II_T287-24-BUILTRITE.pdf Verified By: Farabaugh Engineering and Testing, LLC Test Reports FL47175_R0_TR_T287-24-BUILTRITE.pdf |
|
|
| 47175.2 |
SS200-16 Roof Panel |
SS200-16 Roof Panel, 16" Wide X 24 ga Steel attached to Steel Purlins at 2' Spacing |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +NA/-80.6 PSF Other: Per ASTM E1592 Test over 16 ga Supports located at 2' on centers With Safety Factor of 2.0. Materials and Installation shall be per Sections 1506 And 1507.4 of the 2023 FBC Building Code. |
Installation Instructions FL47175_R0_II_T287-24-BUILTRITE.pdf Verified By: Farabaugh Engineering and Testing, LLC Test Reports FL47175_R0_TR_T287-24-BUILTRITE.pdf |
|
|
| 47175.3 |
SS200-18 Roof Panel |
SS200-18 Roof Panel, 18" Wide X 24 ga Steel attached to Steel Purlins at 6' Spacing |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +NA/-26.0 PSF Other: Per ASTM E1592 Test over 16 ga Supports located at 6' on centers With Safety Factor of 2.0. Materials and Installation shall be per Sections 1506 And 1507.4 of the 2023 FBC Building Code. |
Installation Instructions FL47175_R0_II_T288-24-BUILTRITE.pdf Verified By: Farabaugh Engineering and Testing, LLC Test Reports FL47175_R0_TR_T288-24-BUILTRITE.pdf |
|
|
| 47175.4 |
SS200-18 Roof Panel |
SS200-18 Roof Panel, 18" Wide X 24 ga Steel attached to Steel Purlins at 2' Spacing |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +NA/-67.6 PSF Other: Per ASTM E1592 Test over 16 ga Supports located at 2' on centers With Safety Factor of 2.0. Materials and Installation shall be per Sections 1506 And 1507.4 of the 2023 FBC Building Code. |
Installation Instructions FL47175_R0_II_T288-24-BUILTRITE.pdf Verified By: Farabaugh Engineering and Testing, LLC Test Reports FL47175_R0_TR_T288-24-BUILTRITE.pdf |