| 41159.1 |
1" SunlocEZ 0.032" Aluminum Roof Panel over 15/32 |
1" SunlocEZ 0.032" Aluminum Roof Panel over 15/32" Plywood |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +N/A/-22.7psf Other: -41.7psf @ 5 3/16" O.C.
-32.2psf @ 10 3/8" O.C.
-22.7psf @ 15 9/16" O.C. |
Installation Instructions FL41159_R2_II_Aluminum SunlocEZ Standing Seam over Plywood.pdf Verified By: Johnathan E. Green, P.E. 88223 Created by Independent Third Party: Yes Evaluation Reports FL41159_R2_AE_Aluminum SunlocEZ Standing Seam over Plywood.pdf Created by Independent Third Party: Yes |
|
|
| 41159.2 |
1" SunlocEZ 24 Ga. Roof Panel over 15/32" Plywood |
1" SunlocEZ 24 Ga. Roof Panel over 15/32" Plywood |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +N/A/-41.7psf Other: -101.0psf @ 5 3/16" O.C.
-71.4psf @ 10 3/8" O.C.
-41.7psf @ 15 9/16" O.C. |
Installation Instructions FL41159_R2_II_24 Ga. SunlocEZ Standing Seam over Plywood.pdf Verified By: Johnathan E. Green, P.E. 88223 Created by Independent Third Party: Yes Evaluation Reports FL41159_R2_AE_24 Ga. SunlocEZ Standing Seam over Plywood.pdf Created by Independent Third Party: Yes |
|
|
| 41159.3 |
26 Ga. PBR Roof Panel over Plywood |
26 Ga. PBR Roof Panel over Plywood |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: No Design Pressure: +N/A/-71.0psf Other: 131.0psf @ 8" O.C.
101.0psf @ 12" O.C.
71.0 psf @ 16" O.C. |
Installation Instructions FL41159_R2_II_26 Ga. PBR over Plywood.pdf Verified By: Johnathan E. Green, P.E. 88223 Created by Independent Third Party: Yes Evaluation Reports FL41159_R2_AE_26 Ga. PBR over Plywood.pdf Created by Independent Third Party: Yes |