| 42382.1 |
01: Steel DoubleLok on purlins |
24ga (min) DoubleLok on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-220 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24ga DoubleLok on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24ga DoubleLok on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.2 |
02: Steel Mech Seam purlins |
26ga or 24ga (min) Mech Seam on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-135.3 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24ga Mech Seam on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24ga Mech Seam on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.3 |
03: Steel DoubleLok on purlins |
24ga (min) DoubleLok on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-83.25 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24ga DBL-Lok on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24ga DBL-Lok on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.4 |
04: Steel SuperLok on purlins |
24ga or 22ga (min) SuperLok on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-130 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_22-24ga SuperLok on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_22-24ga SuperLok on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.5 |
05: Steel Secure Seam on purlins |
26ga (min) Secure Seam on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-88.4 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_26ga SecureSeam on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_26ga SecureSeam on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.6 |
06: Steel LokSeam on purlins |
24ga (min) LokSeam on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-40 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24ga LokSeam on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24ga LokSeam on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.7 |
07: Steel Rib panel on purlins |
29ga or 26ga (min) Rib panel on 18ga or 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-47.2 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_26-29ga RIB on 16-18ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_26-29ga RIB on 16-18ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.8 |
08: Steel Rib panel on wood purlins |
29ga (min) Rib panel on 1x4 (min) wood purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-138.9 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_29ga RIB on 1x4 Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_29ga RIB on 1x4 Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.9 |
09: Steel 5V on wood purlins |
29ga (min) 5V panel on 1x4 (min) wood purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-70.25 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_29ga 5V on 1x4 Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_29ga 5V on 1x4 Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.10 |
10: Steel Corrugated on purlins |
26ga or 24ga (min) corrugated panel with nominal 7/8" rib height on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-140 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24-26ga COR on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24-26ga COR on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.11 |
11: Steel 7.2 Panel on purlins |
26ga (min) 7.2 Panel on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-52.5 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_26ga 7-2 Panel on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_26ga 7-2 Panel on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.12 |
12: Steel PBR on purlins |
22ga-29ga PBR on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +96/-163 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_22-29ga PBR on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_22-29ga PBR on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.13 |
13: Steel PBU/M-Panel on purlins |
26ga (min) PBR/M-Panel on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-52.5 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_26ga PBU M Panel on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_26ga PBU M Panel on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.14 |
14: Steel UltraDek on purlins |
24ga (min) UltraDek on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-50 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24ga UltraDek 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24ga UltraDek 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.15 |
15: Steel TS 324 on purlins |
24ga or 22ga (min) TS 324 on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-183.3 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_22-24ga TS 324 on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_22-24ga TS 324 on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.16 |
16: Steel BattenLok HS on purlins |
24ga (min) BattenLok HS on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-71.2 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_24ga BattenLok HS on 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_24ga BattenLok HS on 16ga Purlins.pdf Created by Independent Third Party: Yes |
|
|
| 42382.17 |
17: Steel Retro-R on purlins |
26ga (min) Retro-R on 16ga (min) purlins |
Limits of Use Approved for use in HVHZ: No Approved for use outside HVHZ: Yes Impact Resistant: N/A Design Pressure: +N/A/-130.5 Other: See evaluation report for details. | Approval may be used by any of the Cornerstone Building Brands entities, e.g. Fortify Building Solutions, American Building Components, Ceco Building Systems, MBCI, Metal Sales, Metallic Building Systems, Mueller, Robertson Building Systems, Star Building Systems, Union Corrugating, et al. |
Installation Instructions FL42382_R2_II_26ga RetroR 16ga Purlins.pdf Verified By: David Eng, PE 81377 Created by Independent Third Party: Yes Evaluation Reports FL42382_R2_AE_26ga RetroR 16ga Purlins.pdf Created by Independent Third Party: Yes |