ROOFING
TECHNICAL ADVISORY
Meeting
Minutes
December 2, 2015
1:30 P.M.
 
| TAC
  MEMBERS | 
| TAC MEMBERS Present: CHAIRMAN;
  BRIAN SWOPE, BOB BOYER, WARNER CHANG FOR REMINGTON BROWN, JIMMY BUCKNER,
  BILLY CONE, CHUCK GOLDSMITH, LORRAINE ROSS, KAREN WARSECK, MARK ZEHNAL | 
| Ø Objective: To
  consider, discuss, and provide recommendation for consideration by the Commission
  regarding DS 2015-109 and DS 2015-135 by Robin Davies of Braken
  Engineering | 
 
| MEETING
  Minutes | |
| OBJECTIVE | REVIEW OF OBJECTIVES WILL INCLUDE THE
  FOLLOWING:  Description of issue, discussion by Commission,
  public comment, Commission action. | 
| 1)   | Welcome
  and Opening Remarks | 
| 2) | Roll
  Call | 
| 3) | Reviewed
  and Approved the Meeting Agenda | 
| 4) | Reviewed
  and approved  Minutes of
  October 06, 2015 Roofing TAC Meeting | 
| 5) | TAC  considered, discussed, and provided
  recommendation for consideration by the Commission regarding DS
  2015-109 by Robin Davies of Braken Engineering After
  some lengthy discussion, the TAC voted 6-3 in agreement with the staff’s
  answer.  TAC ACTIONS: Question: Does
  the repair of roof coverings performed in accordance with Chapter 6 of the
  5th Edition (2014) Florida Building Code, Existing Building need to comply
  with the requirements of Section 708 Reroofing?   Answer:  No, as per Section 606.2.1 of the 5th Edition
  (2014) FBC, Existing Building “the Code), the project in question is
  permitted to be restored to its predamage condition
  without meeting the requirements of Section 708.1.1 of the Code.  Building materials to be used in the
  restoration of the project in question must be in accordance with Section
  602.2 of Code. | 
| 6) | TAC  considered, discussed, and provided
  recommendation for consideration by the Commission regarding DS 2015-135 by
  Robin Davies of Braken Engineering After
  some lengthy discussion, the TAC voted 6-3 in agreement with the staff’s
  answer. TAC ACTIONS: Question: Does
  the repair of roof coverings performed in accordance with Chapter 6 of the
  5th Edition (2014) Florida Building Code, Existing Building need to comply
  with the requirements of Section 708 Reroofing?    Answer: No,
  as per Section 606.2.1 of the 5th Edition (2014) FBC, Existing Building “the
  Code), the project in question is permitted to be restored to its predamage condition without meeting the requirements of
  Section 708.1.1 of the Code.  Building
  materials to be used in the restoration of the project in question must be in
  accordance with Section 602.2 of Code. | 
| 7) | General Public Comment- No Public Comment | 
| 8) | General
  Member Comment- No Member comment | 
| 9) | Adjournment. | 
 
STAFF CONTACTS: Robert Benbow, Robert.benbow@myfloridalicense.com, (850) 717-1828;
Mo Madani, mo.madani@myfloridalicense.com, (850) 717-1825.
 
Note: This document is available to any person requiring materials in
alternate format upon request.  Contact the Department of Business
and Professional Regulation, Office of Codes and Standards, 1940 N. Monroe
Street, Suite 90, Tallahassee, Florida 32399-0772 or  call
850-487-1824