DCA06-DEC-182 .

On a motion by Crum with a second by Andrews, the TAC voted to uphold the original recommendations to the Florida Building Commission as follows:

To the question, “Does the referenced code allow the transfer of bathroom exhaust make up air from the corridor to the guest room?” the answer is NO; the TAC voted 4 in favor, 4 opposed .

To the question, “Does the referenced code allow the transfer of bathroom exhaust from the guest room to the bathroom?” the answer is YES; the TAC voted unanimously in favor.

To the question, “Does the referenced code allow the bathroom exhaust to be supplied through the corridor?”, the answer is NO; the TAC voted 4 in favor, 4 opposed.

To the question, “Is the guest room corridor an occupied space?” the answer is NO; the TAC voted 4 in favor, 4 opposed.