| Current Manual/ Settlement | IBHS Draft | Comments | ||||||||||||||||||||||||||||||||||||||||
| 101  Retrofits Required.  Pursuant to Section 553.844, Florida
  Statutes, strengthening of existing site-built, single family residential
  structures to resist hurricanes shall be provided. | 101  Retrofits Required.  Pursuant to Section 553.844, Florida
  Statutes, strengthening of existing site-built, single family residential
  structures permitted prior to the implementation of the 2001  |  | ||||||||||||||||||||||||||||||||||||||||
| 101  Retrofits
  Required.  Pursuant to Section
  553.844, Florida Statutes, strengthening of existing site-built, single
  family residential structures to resist hurricanes shall be provided.  Site built single-
  family residential structures shall mean site built single family detached
  residential structures. |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| 101.1 When a roof on an existing site-built, single family residential structure is replaced: (a) Roof-decking attachment and fasteners shall be strengthened and corrected as required by section 201.1. (b) A secondary water barrier shall be provided as required by section 201.2. | 101.1 When a roof covering on an existing site-built, single family residential structure is replaced: (a)    Roof-decking
  attachment and fasteners shall be strengthened and corrected, in those
  areas of the building where the roof covering is removed, as required by
  section 201.1.    (b) A secondary water barrier shall be provided as required by section 201.2. |  | ||||||||||||||||||||||||||||||||||||||||
| 101.1 When a roof on an existing site-built, single family residential structure is replaced, the following procedures shall be permitted to be performed by the roofing contractor: (a) Roof-decking attachment and fasteners shall be strengthened and corrected as required by section 201.1. (b) A secondary water barrier shall be provided as required by section 201.2. |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| 101.2 When a roof is replaced on a
  building that is located in the wind-borne debris region as defined in s.
  1609.2 of the  (a)  Roof to wall connections shall be improved
  as required by section 201.3.         (b)  Mandated retrofits of the roof-to-wall
  connection shall not be required beyond a 15 percent increase in the cost of
  re-roofing. (c) Where complete retrofits of all the roof-to-wall connections as prescribed in Section 201.3 would exceed 15 percent of the cost of the re-roofing project, the priorities outlined in Section 201.3.5 shall be used to limit the scope of work to the 15 percent limit. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 101.2 When a roof is replaced on a
  building that is located in the wind-borne debris region as defined in s.
  1609.2 of the  (a)  Roof to wall connections shall be improved
  as required by section 201.3.         (b)  Mandated retrofits of the roof-to-wall
  connection shall not be required beyond a 15 percent increase in the cost of
  re-roofing. (c)  Where complete retrofits of all the
  roof-to-wall connections as prescribed in Section 201.3 would exceed 15
  percent of the cost of the re-roofing project, the priorities outlined in
  Section 201.3.7 |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| 101.3 When
  any activity requiring a building permit that is applied for on or after July
  1, 2008, and for which the estimated cost is $50,000 or more for a building
  that is located in the wind borne debris region as defined in s. 1609.2 of
  the  (a)    Opening
  protections as required within the  | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 101.4 When retrofit enhancement of gable end bracing is provided during construction which otherwise requires a permit the techniques in Appendix A shall be allowed. | 101.4  When retrofit enhancement of gable end
  bracing is to be provided  | See Ray Burrough’s
  comment below. See Mike Moore’s
  comment below. | ||||||||||||||||||||||||||||||||||||||||
| 201
  Roof System Mitigation
  Techniques.  Roof sheathing fastening,
  secondary water barriers, roof to wall connection and gable end bracing shall
  be permitted pursuant to this section.  | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 201.1 Roof
  sheathing fastening for site-built
  single family residential structures.  For site-built
  single family residential structures the
  fasteners and spacing required in Table 201.1 are deemed to comply with the
  requirements of Section 507.2.2, of the 2004  | 201.1 Roof decking
    Fastening shall be
  in accordance with section 201.1.1 or 201.1.2. as appropriate for the
  existing construction. 8d nails shall be a minimum of 0.141 inch in diameter
  and shall be a minimum of 2-1/4 inch long to qualify for the provisions of
  this section for existing nails regardless of head shape or head diameter.  | See FRSA comment
  below.  See Mike Moore comment below. | ||||||||||||||||||||||||||||||||||||||||
| Board roof decking
  secured with at least two 8d nails into roof framing members shall be deemed
  to be sufficiently connected.  Board
  roof decking secured with smaller fasteners than 8d nails or with fewer than
  two 8d nails per board shall be deemed sufficiently connected if two 8d
  clipped head, round head, or ring shank nails are in place on each framing
  member.  | 
 |  | ||||||||||||||||||||||||||||||||||||||||
|  | 201.1.1 Roof
  decking consisting of sawn lumber or wood planks up to 12” wide and secured
  with at least two nails (minimum size 8d) to each roof framing member it
  crosses shall be deemed to be sufficiently connected.  Sawn lumber or wood plank decking secured
  with smaller fasteners than 8d nails or with fewer than two nails (minimum size
  8d) to each framing member it crosses shall be deemed sufficiently connected
  if fasteners are added such that two clipped head, round head, or ring shank
  nails (minimum size 8d) are in place on each framing member it crosses.  |  | ||||||||||||||||||||||||||||||||||||||||
|  | 201.1.2 For
  roof decking consisting of wood structural panels, fasteners and spacing
  required in columns 3 and 4 of Table 201.1.2 are deemed to comply with the
  requirements of Section 507.2.2,  |  | ||||||||||||||||||||||||||||||||||||||||
| Supplemental fasteners as required by Table 201.1 shall be 8d
  ring shank nails with round heads and the following minimum dimensions: 1. 0.113 inch nominal shank diameter 2. Ring diameter of 0.012 over shank diameter 3. 16 to 20 rings per inch 4. 0.280 inch full round head diameter 5. 2-1/4 inch nail length | Supplemental fasteners as required by Table 201. 1. 0.113-inch nominal shank diameter 2. Ring diameter a minimum of 0.012-inch 3. 16 to 20 rings per inch 4. a minimum 0.280-inch full
  round head diameter 5. 2-1/4 inch minimum nail length |  | ||||||||||||||||||||||||||||||||||||||||
| Supplemental fasteners as required by Table 201.1 shall be 8d
  ring shank nails with round heads and the following minimum dimensions: 1. 0.113 inch nominal shank diameter 2. Ring diameter of 0.012 over shank diameter 3. 16 to 20 rings per inch 4. 0.280 inch full round head diameter 5. Ring shank to extend a minimum of 1 ½” from the tip of
  the nail. 6. Minimum 2-1/4 inch nail length |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| Table 201.1 Supplement Fasteners at Panel Edges and
  Intermediate Framing 
 a.  Maximum spacing determined based on
  existing fasteners and supplemental fasteners. b.  Maximum spacing determined based on
  supplemental fasteners only. | Table 201.1 Supplement Fasteners at Panel Edges and
  Intermediate Framing 
 a.  Maximum spacing determined based on
  existing fasteners and supplemental fasteners. b.  Maximum spacing determined based on
  supplemental fasteners only. | See below for
  proposed changes in the table. | ||||||||||||||||||||||||||||||||||||||||
| Table 201.1 Supplement Fasteners at Panel Edges and
  Intermediate Framing 
 a.  Maximum spacing determined based on
  existing fasteners and supplemental fasteners. b. 
  Maximum spacing determined based on supplemental fasteners only. |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| 201.2  Roof secondary water barrier for site-built
  single family residential structures.  A
  secondary water barrier shall be installed using one of the following methods
  when roofing replacement when reroofing. 
   | 201.2  Roof secondary water barrier for site-built
  single family residential structures.  A
  secondary water barrier shall be installed using one of the following methods
  during  | See Christ Schulte’s, FRSA’s, Mike Moore’s, and Bill Dumbaugh’s comments below. | ||||||||||||||||||||||||||||||||||||||||
| 201.2  Roof secondary water barrier for site-built
  single family residential structures.  A
  secondary water barrier shall be installed using one of the following methods
  when  |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| a)   All joints in roof sheathing or decking
  shall be covered with a minimum 4 in. wide strip of self-adhering polymer
  modified bitumen tape applied directly to the sheathing or decking.  The deck and self adhering polymer modified
  bitumen tape shall be covered with one of the underlayment systems approved
  for the particular roof covering to be applied to the roof. | a)   No change. |  | ||||||||||||||||||||||||||||||||||||||||
| a)   All joints in structural panel roof
  sheathing or decking shall be covered with a minimum 4 in. wide strip of
  self-adhering polymer modified bitumen tape applied directly to the sheathing
  or decking.  The deck and self adhering
  polymer modified bitumen tape shall be covered with one of the underlayment
  systems approved for the particular roof covering to be applied to the roof. |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| b)   The entire roof deck shall be covered with
  an approved self-adhering polymer modified bitumen cap sheet.  No additional underlayment shall be
  required on top of this cap sheet for new installations. | b)   No change. |  | ||||||||||||||||||||||||||||||||||||||||
| b)   The entire roof deck shall be covered with
  an approved self-adhering polymer modified bitumen  |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| c) The entire roof deck shall be covered with an approved asphalt
  impregnated 30# felt underlayment installed with nails and tin-tabs as
  required for the HVHZ.  (No additional
  underlayment shall be required over the top of this sheet). |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| d) Outside
  of the HVHZ, an underlayment complying with
  section 1507.2.3 of the  |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| EXCEPTIONS: 1.     
  An asphalt impregnated 30# felt underlayment
  installed with nails and tin-tabs as required for the HVHZ and covered with
  either an approved self-adhering polymer modified bitumen cap sheet or an
  approved cap sheet applied using an approved hot-mop application shall be
  deemed to meet the requirements for the secondary water barrier. | EXCEPTIONS: 1.  An asphalt impregnated 30#
  felt underlayment installed  |  | ||||||||||||||||||||||||||||||||||||||||
|  | 2. A
  reinforced synthetic underlayment with an ICC approval as an alternate to
  ASTM D226 felt paper meeting ASTM D1970 nail sealing requirements and having
  a minimum tear strength per ASTM D1970 or ASTM D4533 of 20 lbs.  This underlayment, when attached using
  annular ring or deformed shank roofing fasteners with minimum 1-inch diameter
  metal or plastic caps at the spacing required by the manufacturer for high
  wind installations or code requirements if more stringent; and, when all
  seams are sealed with a compatible adhesive or compatible 4-inch wide tape,
  shall be deemed to meet the requirements for the secondary water barrier. 3.
  Application of a two-part urethane based closed cell spray-on adhesive to the
  attic side of the joints between the sheathing shall be deemed to meet the
  requirements for the secondary water barrier. |  | ||||||||||||||||||||||||||||||||||||||||
| Exceptions: 1. Roof slopes < 2:12 having a continuous roof
  system shall be deemed to comply with section 201.2 requirements for a
  secondary water barrier. 2. Clay and Concrete tile roof systems installed
  as required by the  
 |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| 201.3 Roof-to-wall connections for site-built single family
  residential structures.  Where required by Section 101.2,
  the intersection of roof framing with the wall below shall be strengthened by
  adding metal connectors, clips, straps, and fasteners such that the
  performance level equals or exceeds the uplift capacities as specified in
  Table 201.3.  As an alternative to an
  engineered design, the prescriptive retrofit solutions provided in Sections
  201.3.1 through 201.3.4 shall be accepted as meeting the mandated roof-to-wall
  retrofit requirements. | 201.3 Roof-to-wall connections for site-built single family residential
  structures.   Where required by
  section 101.2, the intersection of roof framing with the wall below shall |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3 Roof-to-wall connections for site-built single family
  residential structures.  Where required by Section 101.2,
  the intersection of roof framing with the wall below shall be strengthened by
  adding metal connectors, clips, straps, and fasteners such that the
  performance level equals or exceeds the uplift capacities as specified in
  Table 201.3.  As an alternative to an
  engineered design, the prescriptive retrofit solutions provided in Sections
  201.3.3 |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| Exceptions: 1.  Where it can be demonstrated (by code
  adoption date documentation and permit issuance date) that roof-to-wall
  connections and/or roof-to-foundation continuous load path requirements were
  required at the time of original construction. 2.   Roof- to- wall
  connections shall not be required unless evaluation and installation of
  connections at gable ends or all corners can be completed for 15% of the cost
  of roof replacement.   |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
|  | 201.3.1 Access
  for Retrofitting Roof to Wall Connections. 
  These provisions are not intended to limit the means for
  gaining access to the structural elements of the roof and wall for the
  purposes of retrofitting the connection.
   The retrofit of roof to wall connections can be made by access
  through the area under the eave, from above through the roof, or from the
  interior of the house.  Methods for
  above access include removal of roof panels or sections thereof or removal of
  portions of roof paneling by in effect making holes at selected locations
  large enough for access, viewing, and installing the retrofit connectors and
  fasteners.   Where panels or sections are removed, the removed
  portions shall not be reused.  New
  paneling shall be used and fastened as in new construction.   Holes shall be deemed adequately repaired if a patch of
  paneling is installed with no gap greater than ½ inch between the patch and
  the existing sheathing and if the patch is supported using one of the
  following methods.   |  | ||||||||||||||||||||||||||||||||||||||||
|  | a)      Solid
  1-1/2 inch lumber shall fully support the patch and shall be secured to the
  existing sheathing with #8 by 1-1/4 inch screws spaced a minimum of 3” around
  the perimeter with screws a minimum of ¾ inch from the near edge of the
  hole.  The patch shall be secured to
  the lumber with #8 x 1-1/4 inch screws spaced on a grid no greater than 6
  inches by 6 inches with no fewer than 2 screws.  b)     
  Holes that extend horizontally from roof
  framing member to adjacent roofing framing member that are less than or equal
  to 7” wide along the slope of the roof 
  shall be supported by minimum of 2x4 lumber whose face is attached to
  each roofing framing members using a minimum of 2 each 3-inch long fasteners
  (#8 screws or  10d common nails)
  connecting the two.  The patch shall
  have attached to its bottom running horizontally a minimum 2x4 either flat wise
  or on edge secured with #8 x 1-1/4 inch screws a maximum of 4 inches on center
  and no more distant from the end of the added lumber than 3 inches.  The patch shall be secured with two #8 x
  1-1/4 inch screws to each support member.   |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.1 Access for Retrofitting Roof to
  Wall Connections.  These provisions are not intended to limit
  the means for gaining access to the structural elements of the roof and wall
  for the purposes of retrofitting the connection.  The retrofit of roof to wall connections can be made by access
  through the area under the eave, from above through the roof, or from the
  interior of the house.  Methods for
  above access include removal of roof panels or sections thereof or removal of
  portions of roof paneling at selected locations large enough for access,
  viewing, and installing the retrofit connectors and fasteners.   Where panels or
  sections are removed, the removed portions shall not be reused.  New paneling shall be used and fastened as
  in new construction.   |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.2  Partially inaccessible straps:  Where part of a strap is inaccessible,
  if the portion of the strap that is observed is fastened in compliance with
  these requirements, the inaccessible portion of the strap shall be presumed
  to comply with these requirements.  |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.1 Prescriptive method for gable roofs
  on a wood frame wall.  Sufficient eave sheathing shall be removed
  to expose a minimum of 6-feet of framing members, measured from the corner,
  along the exterior wall on each side of each gable end.  The anchorage of each of the exposed
  rafters or truss shall be inspected.  Wherever
  a strap is missing or an existing strap has fewer than four fasteners on each
  end, approved straps, ties or right angle gusset brackets with a minimum
  uplift capacity of 500 lbs shall be installed that connect each rafter or
  truss to the top plate below.  Adding
  fasteners to existing straps shall be allowed in lieu of adding a new strap
  provided the strap is manufactured to accommodate at least 4 fasteners at
  each end.  Wherever access makes it
  possible (without damage of the wall or soffit finishes), both top plate
  members shall be connected to the stud below using a stud to plate connector
  with a minimum uplift capacity of 500 lbs. | 201.3.2 |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.3 |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| 201.3.2 Prescriptive method for gable roofs
  on a masonry wall.  Sufficient eave sheathing shall be removed
  to expose a minimum of 6-feet of framing members, measured from the corner,
  along the exterior wall on each side of each gable end.  The anchorage of each of the exposed
  rafters or truss shall be inspected.  Wherever
  a strap is missing or an existing strap has fewer than four fasteners on each
  end, approved straps, ties or right angle gusset brackets with a minimum
  uplift capacity of 500 lbs shall be installed that connect each rafter or
  truss to the top plate below or directly to the masonry wall using approved
  masonry screws that will provide at least a 2-1/2 embedment into the concrete
  or masonry.  When the straps or right
  angle gusset brackets are attached to a wood sill plate, the sill plate shall
  be anchored to the concrete masonry wall below.  This anchorage shall be accomplished by
  installing ¼-inch diameter masonry screws, each with supplementary ¼-inch
  washer, having sufficient length to develop a 2-1/2 inch embedment into the
  concrete and masonry.  These screws
  shall be installed within 4-inches of the truss or rafter on both sides of
  each interior rafter or truss and on the accessible wall side of the gable
  end truss or rafter. | 201.3.3 |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.4 |  | Settlement | ||||||||||||||||||||||||||||||||||||||||
| 201.3.3 Prescriptive method for hip roofs
  on a wood frame wall.  Sufficient corner eave sheathing shall be
  removed from the side of the hip ridge parallel to the roof ridge to provide
  access to a minimum 6-foot length of the exterior wall.  The hip ridge board and any exposed rafters
  that are not anchored with a strap having at least four fasteners on each
  end, shall be connected to the top plate below using a strap or a right angle
  gusset bracket having a minimum uplift capacity of 500 lbs.  Adding fasteners to existing straps shall
  be allowed in lieu of adding a new strap provided the strap is manufactured
  to accommodate at least 4 fasteners at each end.   Wherever access makes it possible (without
  damage of the wall or soffit finishes), both top plate members shall be
  connected to the stud below using a stud to plate connector with a minimum
  uplift capacity of 500 lbs. | 201.3. |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.5 |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.4 Prescriptive method for hip roofs
  on a masonry wall.  Sufficient corner eave sheathing shall be
  removed from the side of the hip ridge parallel to the roof ridge to provide
  access to a minimum 6-foot length of the exterior wall.  The hip ridge board and any exposed rafters
  that are not anchored with a strap having at least four fasteners on each
  end, shall be connected to the concrete masonry wall below using approved
  straps or right angle gusset brackets with a minimum uplift capacity of 500
  lbs.  Adding fasteners to existing
  straps shall be allowed in lieu of adding a new strap provided the strap is
  manufactured to accommodate at least 4 fasteners at each end.  The straps or right angle gusset brackets
  shall be installed such that they connect each rafter or truss to the top
  plate below or directly to the masonry wall using approved masonry screws
  that will provide at least a 2-1/2 embedment into the concrete or
  masonry.  When the straps or right
  angle gusset brackets are attached to a wood sill plate, the sill plate shall
  be anchored to the concrete masonry wall below.  This anchorage shall be accomplished by
  installing ¼-inch diameter masonry screws, each with supplementary ¼-inch
  washer, with sufficient length to develop a 2-1/2 inch embedment into the
  concrete and masonry.  These screws
  shall be installed within 4-inches of the truss or rafter on both sides of
  each interior rafter or truss and on the accessible wall side of the gable
  end truss or rafter. | 201.3.5 |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.6 |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.5 Priorities for mandated
  roof-to-wall retrofit expenditures.  For houses with both hip and
  gable roof ends, the priority shall be to retrofit the gable end roof-to-wall
  connections unless the width of the hip end is more than 1.5 times greater
  than the width of the gable end.  Priority
  shall be given to connecting the corners of roofs to walls below where the
  spans of the roofing members are greatest. | 201.3.6 |  | ||||||||||||||||||||||||||||||||||||||||
| 201.3.7 |  | Settlement  | ||||||||||||||||||||||||||||||||||||||||
| Table
  201.3 Required Uplift Capacities for Roof-to-Wall
  Connections (POUNDS PER LINEAR FOOT) |  | See table and Ray
  Burrow’s comment below. | ||||||||||||||||||||||||||||||||||||||||
| A101.1  Intent and purpose.  The provisions of this subsection provide prescriptive solutions for
  the retrofitting of gable ends of buildings. The retrofit measures are not
  intended to provide strengthening  | A101.1  Intent and purpose.  The provisions of this subsection provide prescriptive solutions for
  the retrofitting of gable ends of buildings. The retrofit measures are  |  | ||||||||||||||||||||||||||||||||||||||||
| A101.2  Scope. 
  The following
  prescriptive methods are intended for applications where the gable end wall
  framing is provided by a wood gable end wall truss or a conventionally framed
  rafter system.  The retrofits are
  appropriate for wall studs oriented with their broad face parallel to or
  perpendicular to the gable wall surface. 
  An overview perspective drawing of the retrofit is shown in Figure
  A104.1. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| ANCHOR BLOCK.  A nominal 2-inch  thick by at least 4” wide piece of lumber
  secured to horizontal braces and filling the gap between existing framing
  members for the purpose of restraining horizontal braces from movement perpendicular
  to the framing members. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| COMPRESSION
  BLOCK.  A nominal 2-inch  thick
  by at least 4” wide piece of lumber used to restrain in the
  compression mode (force directed towards the interior of the attic) an
  existing or retrofit stud.  It is
  attached to a horizontal brace and bears directly against the existing or
  retrofit stud. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| CONVENTIONALLY
  FRAMED GABLE END.  A conventionally framed gable end with
  studs whose faces are perpendicular to the gable end wall. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| HORIZONTAL
  BRACE.   A nominal 2-inch  thick
  by at least 4” wide piece of lumber used to restrain both compression
  and tension loads applied by a retrofit stud. 
  It is typically installed horizontally on the top of floor framing
  members (truss bottom chords or ceiling joists) or on the bottom of pitched
  roof framing members (truss top chord or rafters).  | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| RETROFIT STUD.  A
  nominal 2-inch lumber member used to structurally supplement an existing
  gable end wall stud. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| RIGHT ANGLE GUSSET BRACKET.  A
  14 gage or thicker metal right angle bracket with a minimum load capacity
  perpendicular to the plane of either face of 350 lbs when connected to wood
  or concrete with manufacturer specified connectors. | RIGHT ANGLE  |  | ||||||||||||||||||||||||||||||||||||||||
| STUD-TO-PLATE CONNECTOR.  A
  manufactured metal connector designed to connect studs to plates with a
  minimum uplift capacity of 500 lbs. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| TRUSS GABLE
  END.  An engineered factory made truss or site
  built truss that incorporates factory installed or field installed vertical
  studs with their faces parallel to the plane of the truss and are spaced no
  greater than 24-inches on center.  Web
  or other diagonal members other than top chords may or may not be
  present.  Gable end trusses may be of
  the same height as nearby trusses or may be drop chord trusses in which the
  top chord of the truss is lower by the depth of the top chord or outlookers. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.1  Existing materials. All existing wood materials
  that will be part of the retrofitting work (trusses, rafters, ceiling joists,
  top plates, wall studs, etc.) shall be in sound condition and free from
  defects or damage that substantially reduce the load-carrying capacity of the
  member.  Any wood materials found to be
  damaged or deteriorated shall be strengthened or replaced with new materials
  to provide a net dimension of sound wood equivalent to its undamaged original
  dimensions. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.2 
  New Materials.  All materials approved by
  this code, including their appropriate allowable stresses, shall be permitted
  to meet the requirements of this chapter. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.3 Dimensional Lumber.  All dimensional lumber for braces, studs,
  and blocking shall conform to applicable standards or grading rules.  Dimensional lumber shall be identified by a
  grade mark of a lumber grading or inspection agency that has been approved by
  an accreditation body that complies with DOC PS 20.  All new dimensional lumber to be used for
  retrofitting purposes shall be a minimum grade and species of #2
  Spruce-Pine-Fir or shall have a specific gravity of 0.42 or greater.  In lieu of a grade mark, a certificate of
  inspection issued by a lumber grading or inspection agency meeting the
  requirements of this code shall be accepted. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.4 Metal Plate
  Connectors, Straps and Anchors. Metal
  plate connectors, straps and anchors shall have product approval.  They shall be approved for connecting
  wood-to-wood or wood-to-concrete as appropriate.  Straps
  and tie plates shall be manufactured from galvanized steel with a minimum
  thickness provided by 20 gauge.  Tie
  plates shall have holes sized for 8d nails. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.5 Twists
  in straps.  Straps shall be permitted to be
  twisted 90 degrees in addition to a 90 degree bend where they transition
  between framing members or connection points. 
   | A103.5 Twists
  in straps.  Straps shall be permitted to be
  twisted 90 degrees in addition to a 90 degree bend where they transition
  between framing members or connection points. 
  Straps shall be bent only once at a given location though it is
  permissible that they be bent or twisted at multiple locations along their
  length. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.6  Fasteners. Fasteners
  meeting the requirements of Sections A103.6.1 and A103.6.2 shall be used and
  shall be permitted to be screws or nails meeting the minimum length
  requirement shown in figures and specified in tables.   | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.6.1
  Screws.  Screws shall be a minimum #8
  size with head diameters no
  less than 0.3 inch.   Screw lengths
  shall be no less than indicated in the Figures and in Tables.  Permissible
  screws include deck screws, wood screws, or sheet metal screws
  (without drill bit type tip, but can be sharp pointed).  Screws shall have at least 1 inch of
  thread.  Fine threaded screws or
  drywall screws shall not be permitted. 
  Note that many straps will not accommodate screws larger than #8. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.6.2 Nails.  Unless otherwise indicated in the
  provisions or drawings, where fastener lengths are indicated in Figures and Tables as 1-¼ inch, 8d common nails with shank diameter 0.131 inch and head
  diameters no less than 0.3 inch shall be permitted.  Unless otherwise indicated in the
  provisions or drawings, where fasteners lengths are indicated in Figures
  and Tables as 3 inch, 10d common
  nails with shank diameter of 0.148 inch and head diameters no less than 0.3
  inch shall be permitted.   | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A103.7 Fastener
  spacing.  Fastener spacing shall be as
  follows: a) distance between fasteners and the edge of lumber shall be a minimum of ½
  inch unless otherwise indicated,   b) distance between fasteners and the end of lumber shall be a minimum
  of 2-½ inch,  c)  distance between fasteners
  parallel to grain (center-to-center) when straps are not used shall be a
  minimum of 2-1/2 inches unless a ½-inch stagger (perpendicular to the grain)
  is applied for adjacent fasteners, then the distance between fasteners
  parallel to the grain shall be a minimum of 1-1/4 inches.   d). distance between fasteners across grain (row spacing) when straps
  are not used shall be a minimum of 1 inch, and the   e) distance between fasteners inserted in metal plate connectors,
  straps and anchors as defined in Section A103.4 shall be those provided by
  holes manufactured into the straps.  | A103.7 Fastener
  spacing.  Fastener spacing shall be as
  follows: a) distance between fasteners and the edge of lumber shall be a minimum of ½
  inch except where the holes in straps place fasteners closer to the
  edge.  In that case, the minimum shall
  be1/4 inch unless otherwise indicated,   b) distance between fasteners and the end of lumber shall be a minimum
  of 2-½ inch,  c)  distance between fasteners
  parallel to grain (center-to-center) when straps are not used shall be a
  minimum of 2-1/2 inches unless a ½-inch stagger (perpendicular to the grain)
  is applied for adjacent fasteners, then the distance between fasteners
  parallel to the grain shall be a minimum of 1-1/4 inches.   d). distance between fasteners across grain (row spacing) when straps
  are not used shall be a minimum of 1 inch, and the   e) distance between fasteners inserted in metal plate connectors,
  straps and anchors as defined in Section A103.4 shall be those provided by
  holes manufactured into the straps.   |  | ||||||||||||||||||||||||||||||||||||||||
| A104.1  Scope and intent. 
  Gable ends to be strengthened shall be permitted to be retrofitted
  using methods prescribed by provisions of this section.  These prescriptive methods of retrofitting
  are intended to increase the resistance of existing gable end wall
  construction for out-of-plane wind loads resulting from high wind
  events.  The retrofit method addresses
  four issues.  These include
  strengthening the framing members of the walls if necessary (retrofit studs),
  bracing the top and bottom of the gable wall so that lateral loads are
  transmitted into the roof and ceiling diaphragms (horizontal braces, straps
  to retrofit studs and compression blocks) and connecting the bottom of the
  gable end wall to the wall below to help brace the top of that wall
  (specialty metal brackets). | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| The following prescriptive methods are intended for applications
  where the gable end wall framing is provided by a wood gable end wall truss
  or a conventionally framed rafter system. 
  The retrofits are appropriate for wall studs oriented with their broad
  face parallel to or perpendicular to the gable wall surface.  An overview perspective drawing of the
  retrofit is shown in Figure A104.1. |  |  | ||||||||||||||||||||||||||||||||||||||||
| A104.2 Horizontal Braces.  Horizontal braces shall be installed
  approximately perpendicular to the top and bottom chords of the existing roof
  trusses or approximately perpendicular to the rafters and ceiling joists at
  the location of each existing gable end wall stud greater than 3-feet in
  length.  If the spacing of existing
  gable end studs is greater than 24 inches or no vertical gable end stud is
  present, a stud and horizontal braces shall be installed such that the
  maximum spacing between existing and added studs shall be 24–inches.  Additional gable end wall studs shall not
  be required at locations where their length would be 3-feet or less.  Each required added stud shall be attached
  to the existing roofing framing members (truss top chord or rafter and truss
  bottom chord or ceiling joist) using a minimum of two 3-inch toenail
  fasteners (#8 wood screws or 10d nails) and a metal connector or mending
  plate with a minimum of four 1-1/4 inch long fasteners (#8 wood screws or 8d
  nails) at each end.   The horizontal
  braces shall consist of the minimum size member indicated in Table
  A104.2.  The horizontal brace shall be
  oriented with their long face across the top and bottom chords of the wood
  trusses (or rafters and ceiling joists) and extend a minimum of three framing
  spacings from the gable end wall plus 2-1/2 inch beyond the last top chord or
  bottom chord member (rafter or ceiling joist) as shown in Figure A104.2.1
  (and A104.2.6).  The horizontal brace
  shall be located no farther than ½ inch from the inside face of
  the gable end wall truss.   Each
  horizontal brace shall be fastened to each existing framing member (top chord
  or rafter or bottom chord or ceiling joist) that it crosses using three
  3-inch long fasteners (#8 wood screws or 10d nails) as indicated in Figures
  A104.2.2 through A104.2.5 for trusses (and Figures A104.2.7 through A104.2.10
  for rafters). | A104.2 Horizontal Braces.  Horizontal braces shall be installed
  approximately perpendicular to the roof and ceiling framing members at the
  location of each existing gable end wall stud greater than 3-feet in
  length.   The horizontal
  braces shall consist of the minimum size member indicated in Table
  A104.2.  The horizontal braces shall be
  oriented with their wide faces across the roof or ceiling framing members, be
  fastened to a minimum of three framing members, and extend at least 6-feet
  measured perpendicularly from the gable end wall plus 2-1/2 inch beyond the
  last top chord or bottom chord member (rafter or ceiling joist) from the
  gable end wall as shown in Figure A104.2.1 (and A104.2.6).  The horizontal brace shall be located no
  farther than ½ inch from the inside face of the gable end wall
  truss.   Each horizontal brace shall be
  fastened to each existing roof or ceiling member that it crosses using three
  3-inch long fasteners (#8 wood screws or 10d nails) as indicated in Figures
  A104.2.2 through A104.2.5 for trusses (and Figures A104.2.7 through A104.2.10
  for conventionally framed). If the spacing
  of existing gable end studs is greater than 24 inches or no vertical gable
  end stud is present, a new stud and corresponding horizontal braces shall be
  installed such that the maximum spacing between existing and added studs
  shall be 24–inches.  Additional gable end wall studs shall not
  be required at locations where their length would be 3-feet or less.  Each end of each required new stud shall be
  attached to the existing roofing framing members (truss top chord or rafter
  and truss bottom chord or ceiling joist) using a minimum of two 3-inch
  toenail fasteners (#8 wood screws or 10d nails) and a metal connector or
  mending plate with a minimum of four 1-1/4 inch long fasteners (#8 wood
  screws or 8d nails).    |  | ||||||||||||||||||||||||||||||||||||||||
|  | 
 |  | ||||||||||||||||||||||||||||||||||||||||
| Exceptions:   1.   Where obstructions, other permanently
  attached obstacles or conditions exist that will not permit installation of
  new horizontal braces at the indicated locations, refer to Section A104.5 for
  permitted modification of these prescriptive retrofit methods. | Exceptions:   1.  Where impediments
   |  | ||||||||||||||||||||||||||||||||||||||||
| 2.  Where obstructions, other permanently
  attached obstacles or conditions exist that will not permit extension of the
  new horizontal braces across the existing framing members a minimum of three
  framing spaces from the gable end wall, the horizontal braces may be
  shortened provided that all of the following conditions are met. | 2. Where impediments  |  | ||||||||||||||||||||||||||||||||||||||||
| a.  The horizontal brace shall
  be installed across a minimum of two framing spaces and fastened to each
  existing framing member with three 3-inch long fasteners (#8 wood screws or
  10d nails). | a.  The horizontal brace shall be installed
  across a minimum of two framing spaces, fastened to each existing framing
  member with three 3-inch long fasteners (#8 wood screws or 10d nails), and
  extend a minimum of 4-feet from the gable end wall. |  | ||||||||||||||||||||||||||||||||||||||||
| b. The minimum size of the anchor block
  shall be equivalent to the existing framing members.  The anchor block shall be fastened to the
  side of the horizontal brace in the second framing space from the gable end
  wall as shown in Figure A104.2.11.  Six
  3-inch long fasteners (#8 wood screws or 10d nails) shall be used to fasten
  the anchor block to the side of the horizontal brace. | b.   |  | ||||||||||||||||||||||||||||||||||||||||
| c.  The
  anchor block shall extend beyond the surface of the horizontal brace that is
  in contact with the existing framing members  | c.  The anchor block shall extend into
  the space between the roof or ceiling framing members a minimum of one-half the depth of  |  | ||||||||||||||||||||||||||||||||||||||||
| A104.3 Retrofit Studs.  The
  retrofit studs shall consist of the minimum size members for the height
  ranges of the existing vertical gable end wall studs indicated in Table
  A104.2.  Retrofit studs shall be
  installed adjacent to the existing or added (Section A104.2) vertical gable
  end wall studs and extend from the top of the lower horizontal brace to the
  bottom of the upper horizontal brace. 
  A maximum gap of 1/8-inch shall be permitted between the retrofit stud
  and the bottom horizontal brace.  A
  maximum gap of ½-inch shall be permitted between the top edge of the retrofit
  stud closest to the upper horizontal brace and the horizontal brace surface. Exception:   Where  | A104.3 Retrofit Studs.  The
  retrofit studs shall consist of the minimum size members for the height
  ranges of the existing vertical gable end wall studs indicated in Table
  A104.2.  Retrofit studs shall be
  installed adjacent to the existing or added (Section A104.2) vertical gable
  end wall studs and extend from the top of the lower horizontal brace to the
  bottom of the upper horizontal brace. 
  A maximum gap of 1/8-inch shall be permitted between the retrofit stud
  and the bottom horizontal brace.  A
  maximum gap of ½-inch shall be permitted between the top edge of the retrofit
  stud closest to the upper horizontal brace and the horizontal brace surface. Exception:   Where impediments  |  | ||||||||||||||||||||||||||||||||||||||||
| A104.3.1 Retrofit Stud Fastening. 
  Each retrofit stud shall be fastened to the top and bottom horizontal
  brace members with a minimum of a 20 gauge, 11/4 inch
  wide flat metal strap with pre-punched fastener holes.  The flat metal straps shall be the minimum
  length as indicated in Table A104.2. 
  Each top and bottom strap shall extend sufficient distance onto the
  vertical face of the retrofit stud and be fastened with the number of 1-1/4
  inch long fasteners (#8 wood screws or 8d nails) indicated in Table
  A104.2.  Each strap shall be fastened
  to the top and bottom horizontal brace members with the minimum number of
  1-1/4 inch long fasteners (#8 wood screws or 8d nails) as indicated in Table
  A104.2.  The retrofit stud members
  shall also be fastened to the side of the existing vertical gable end wall
  studs with 3-inch long fasteners (#8 wood screws or 10d nails) spaced at
  6-inches on center as shown in Figure A104.2.1. | A104.3.1 Retrofit Stud Fastening. 
  Each retrofit stud shall be fastened to the top and bottom horizontal
  brace members with a minimum of a 20 gauge, 1-1/4 inch wide flat or coil
  metal strap with pre-punched fastener holes. 
  The flat metal straps
  shall be the minimum length as indicated in Table A104.2.  Each top and bottom strap shall extend
  sufficient distance onto the vertical face of the retrofit stud and be
  fastened with the number of 1-1/4 inch long fasteners (#8 wood screws or 8d
  nails) indicated in Table A104.2.  Each
  strap shall be fastened to the top and bottom horizontal brace members with
  the minimum number of 1-1/4 inch long fasteners (#8 wood screws or 8d nails)
  as indicated in Table A104.2.  The
  retrofit stud members shall also be fastened to the side of the existing
  vertical gable end wall studs with 3-inch long fasteners (#8 wood screws or
  10d nails) spaced at 6-inches on center as shown in Figure A104.2.1. |  | ||||||||||||||||||||||||||||||||||||||||
| A104.3.2 Retrofit Stud Splices. 
  Retrofit studs greater than 8-feet in height may be field spliced as
  shown in Figure A104.3. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A104.4 Compression Blocks.  Compression
  blocks shall have minimum lengths as indicated in Table A104.2.  Compression blocks shall be installed on
  the horizontal braces directly against either the existing vertical gable end
  wall stud or the retrofit stud.  For
  clarity, Figures A104.2.2 through A104.2.5 (trusses) and Figures A104.2.7
  through A104.2.10 (rafters) show the installation of the compression block
  against the existing vertical gable end wall stud with the strap from the
  retrofit stud running beside the compression block.  When the compression block is installed
  against the retrofit stud, the block shall be allowed to be placed on top of
  the strap.  A maximum gap between the
  compression block and the existing vertical gable end wall stud member or
  retrofit stud of 1/8 inch shall be permitted.  Compression blocks shall be fastened to the
  horizontal braces with the minimum number of 3-inch long fasteners (#8 wood
  screws or 10d nails). End and edge distances for fastener installation shall
  be as listed in Section A103.7 and shown in Figures A104.2.2 through A104.2.5
  (trusses) and Figures A104.2.7 through A104.2.10 (rafters). | A104.4 Compression Blocks.   |  | ||||||||||||||||||||||||||||||||||||||||
| A104.5 Obstructions
  – Permissible modifications to prescriptive gable end retrofits.  Where obstructions, other permanently attached obstacles or conditions exist in attics that preclude the
  installation of a retrofit stud or horizontal braces in accordance with
  Sections A104.2 or A104.3, the gable end retrofit shall be deemed to meet the
  requirements of this section if the requirements of Section A104.5.1 are met.  Obstructions to the installation of
  retrofit studs or horizontal braces include gable end vents, attic accesses,
  recessed lights, skylight shafts, chimneys, air conditioning ducts, or
  equipment.  Where the installation of a
  horizontal brace for the top of a center stud is obstructed by truss plates
  near the roof peak, methods prescribed in A104.5.1 are permitted to be used,
  or retrofit ridge ties as prescribed in Section A104.5.2 are permitted to be
  used to support the horizontal brace.  | A104.5 Impediments |  | ||||||||||||||||||||||||||||||||||||||||
| A104.5.1
  Remedial measures where obstacles prevent installation of retrofit studs or
  horizontal braces.  If a
  retrofit stud or horizontal brace cannot be installed because of an obstruction,
  the entire assembly can be omitted from that location provided all of the
  following conditions are met. | A104.5.1
  Remedial measures where obstacles prevent installation of retrofit studs or
  horizontal braces.  If a
  retrofit stud or horizontal brace cannot be installed because of an impediment |  | ||||||||||||||||||||||||||||||||||||||||
| 1.   No more than two
  assemblies of retrofit studs and horizontal braces are omitted on a single
  gable end. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 2.   There shall be at
  least two retrofit studs and horizontal brace assemblies on either side of
  the locations where the retrofit studs and horizontal bracing members are
  omitted (no two ladder braces bearing on a single retrofit stud). | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 3.   The retrofit
  studs on each side of the omitted retrofit stud are increased to the next
  indicated member size in Table A104.2 and fastened as indicated in Section
  A104.3.1. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 4.   The horizontal
  bracing members on each side of the omitted brace shall be sized in
  accordance with Table A104.2 for the required retrofit studs at these
  locations. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 5.   The horizontal
  bracing members on each side of the omitted brace shall extend a minimum of
  three framing spaces from the gable end wall unless anchor blocks are
  installed in accordance with Exception 2 of Section A104.2. | 5.  The horizontal bracing members on each side
  of the omitted brace shall meet
  the requirements  |  | ||||||||||||||||||||||||||||||||||||||||
| 6.   Ladder bracing is
  provided across the location of the omitted retrofit studs as indicated in
  Figures A104.5.1.1 (trusses) and A104.5.1.2 (rafters). | 6. No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 7.   Ladder bracing
  shall consist of a minimum 2x4 members oriented horizontally and spaced at
  12-inches on center vertically.  Ladder
  bracing shall be attached to each adjacent retrofit stud with a metal framing
  angle with a minimum lateral capacity of 175 lbs.  Ladder bracing shall be attached to the
  existing stud at the location of the omitted retrofit stud with a metal
  hurricane tie with a minimum capacity of 175 lbs. | 7.  Ladder
  bracing shall consist of a minimum 2x4 members oriented horizontally and
  spaced a maximum  |  | ||||||||||||||||||||||||||||||||||||||||
| 8.   Where ladder
  bracing spans across a gable end vent, no attachment to the gable end vent
  framing shall be required. | 8.  Where
  ladder bracing spans across a gable end vent, the gable end vent framing
  shall be attached to the ladder bracing using metal straps or clips.   |  | ||||||||||||||||||||||||||||||||||||||||
| 9.   Notching of the
  ladder bracing shall not be permitted. | 9.  Notching
  of the ladder bracing shall not be permitted unless the net depth of the
  framing member is a minimum of 3-1/2 inches. |  | ||||||||||||||||||||||||||||||||||||||||
| A104.5.2
  Retrofit ridge ties.  When obstructions
  along the ridge of the roof obstruct the installation of a horizontal brace
  for one or more studs near the middle of the gable wall, retrofit ridge ties
  may be used to provide support for the required horizontal brace.  Retrofit ridge tie members shall be installed a maximum of 12 inches
  below the existing ridge line.  The
  retrofit ridge tie members shall be installed across a minimum of three bays
  to permit fastening of the horizontal brace. 
  A minimum of a 2x4 member shall be used for each ridge tie and
  fastening shall consist of two 3-inch long wood screws, four 3-inch long 10d
  nails or two 3-1/2 inch long 16d nails driven through and clinched at each
  top chord or web member intersected by the ridge tie as illustrated in Figure
  A104.5.2. | A104.5.2
  Retrofit ridge ties.  When impediments  |  | ||||||||||||||||||||||||||||||||||||||||
| A104.5.3
  Notching of retrofit studs.  Retrofit studs may be notched in one
  location along the height of the stud member provided that all of the
  following conditions are met. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 1.   The retrofit stud to be notched shall be
  sized such that the remaining depth of the member at the location of the
  notch (including cut lines) shall not be less than that required by Table
  A104.2.  | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 2.  
  The
  notched retrofit stud shall not be spliced within 12 inches of the location
  of the notch.  The splicing member
  shall not be notched and shall be installed as indicated in Figure A104.3. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 3.  
  The
  length of the flat metal straps indicated in Table A104.2 shall be increased
  by the increased depth of the notched retrofit stud member to be installed. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 4.  
  The
  height of the notch shall not exceed 12 inches vertically as measured at the
  depth of the notch. | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 5.  
  The
  notched retrofit stud member shall be fastened to the side of the existing
  gable end wall studs in accordance with Section A104.3.1.  Two additional 3-inch fasteners (#8 wood
  screws or 10d nails) shall be installed on each side of the notch in addition
  to those required by Section A104.3.1.  | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A104.6
  Connection of gable end wall to wall below. The bottom
  chords or bottom members of wood framed gable end walls shall be attached to
  the wall below using one of the methods prescribed in Sections A104.6.1 or
  A104.6.2.  The particular method chosen
  shall correspond to the framing system and type of wall construction
  encountered.  Due to access
  considerations, this retrofit needs to be carried out before any of the other
  gable end retrofit activities referenced in Sections A104.2, A104.3, A104.4
  or A104.5. | A104.6 Connection
  of gable end wall to wall below. The bottom chords or bottom members of
  wood framed gable end walls shall be attached to the wall below using one of
  the methods prescribed in Sections A104.6.1 or A104.6.2.  The particular method chosen shall correspond
  to the framing system and type of wall construction encountered.   |  | ||||||||||||||||||||||||||||||||||||||||
| A104.6.1 Truss
  gable end wall.  The bottom chords of the
  gable end wall shall be attached to the wall below using right angle gusset brackets
  consisting of 14 gage or thicker material with a minimum load capacity of 350
  lbs perpendicular to the plane of either face of the connector.  The right angle gusset brackets shall be
  installed throughout the portion of the gable end where the gable end wall
  height is greater than 3 feet at the spacing specified in Table A104.6.  A minimum of two of the fasteners specified
  by the manufacturer shall engage the body of the bottom chord.  Connection to the wall below shall be by one
  of the methods listed below: | A104.6.1 Truss
  gable end wall.  The bottom chords of the
  gable end wall shall be attached to the wall below using right angle  |  | ||||||||||||||||||||||||||||||||||||||||
| 
 | 1.  For
  a wood frame wall below,  |  | ||||||||||||||||||||||||||||||||||||||||
| 
 | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| 
 | No change. |  | ||||||||||||||||||||||||||||||||||||||||
| A104.6.2
  Conventionally framed gable end wall. Each stud in a conventionally framed
  gable end wall, throughout the length of the gable end wall where the wall
  height is greater than 3-feet, shall be attached to the bottom or sill plate
  using a stud to plate connector.  The
  bottom or sill plate shall then be connected to the wall below using one of
  the methods listed below: | A104.6.2
  Conventionally framed gable end wall. Each stud in a conventionally framed
  gable end wall, throughout the length of the gable end wall where the wall
  height is greater than 3-feet, shall be attached to the bottom or sill plate
  using a stud to plate connector.  The
  bottom or sill plate shall then be connected to the wall below using one of
  the methods listed below: |  | ||||||||||||||||||||||||||||||||||||||||
| 
 | 1.  For
  a wood frame wall below,  |  | ||||||||||||||||||||||||||||||||||||||||
| 
 | No
  change. |  | 
Table 201.1
Supplement Fasteners at Panel Edges and
Intermediate Framing
| Existing fasteners | Existing spacing | Wind speed 110 mph or less supplemental fastening shall be no greater than | Wind speed greater than 110 mph supplemental fastening shall be no greater than | 
| Staples or 6d  | Any | 6” o.c. b | 6” o.c. b | 
| 8d clipped head, round
  head, or ring shank | 6” o.c. or less | None necessary | None necessary | 
| 8d clipped head or round
  head | Greater than  6” o.c. | 6” o.c.a  | 6” o.c. | 
| 8d round head ring shank | Greater than 6” o.c. | 6” o.c.a  | 6” o.c.a  | 
a.  Maximum spacing determined based on existing
fasteners and supplemental fasteners.
b.  Maximum spacing determined based on
supplemental fasteners only.
Proposed Change:
Table 201.1
Supplement Fasteners at Panel Edges and
Intermediate Framing
| Existing fasteners | Existing spacing | Wind speed 110 mph or less supplemental fastening shall be no greater than | Wind speed greater than 110 mph supplemental fastening shall be no greater than | 
| Staples or 6d  | Any | 6” o.c. b | 6” o.c. b | 
| 8d clipped head, round
  head, or ring shank | 6” o.c. or less | None necessary | None necessary | 
| 
 | Greater than  6” o.c. | 6” o.c.a  | 6” o.c. | 
| 
 
 | 
 
 | 
 | 
 | 
a.  Maximum spacing determined based on existing
fasteners and supplemental fasteners.
b.  Maximum spacing determined based on supplemental
fasteners only.
Table 201.3
Required
Uplift Capacities for Roof-to-Wall Connections
(POUNDS
PER LINEAR FOOT)

Notes:
a.  The required capacities are pounds per lineal
foot of building length.  For roof
framing spaced at 16 inches on center multiply table values by 1.33.  For roof framing spaced at 24 inches on
center multiply table values by 2.
b.  The required capacities include an allowance
for 10 pounds of dead load.
c.  The required capacities do not account for
the effects of overhangs.  The overhang
loads given shall be multiplied by the overhang projection and added to the required
capacities in the table.
Ray
Burroughs’ Comment:
Section 101.4, if gable end bracing is voluntary as you
indicated, this section needs to better indicate such.  As written the retrofit is required as a part
of a project involving “construction which otherwise requires a permit”. Thus
if they are doing any type of activity requiring a permit it would trigger
gable wind bracing for example replacing their air conditioner, replacing their
elect panel, etc.
Mike
Moore’s Comment:
101.5 When a home inspector inspects an existing home as
part of a real estate transaction and determines that the roof decking
attachment does not meet the requirements of Section 201.1, adhesives shall be
used to strengthen the decking attachment per Section 201.2, unless the roof is
being replaced per Section 101.1.
FRSA Comment:
Replace language with the following:
201.1
Roof sheathing fastening for site-built single family residential structures.  Roof sheathing shall be fastened to meet the
requirements of chapters 16 and 23 of the 
Add the following to chapter 15:
1510.1.1
Roof sheathing shall be fastened to meet the requirements of chapter 16 and 23
of the 
Mike Moore’s Comment:
201.1 Roof sheathing
fastening for site-built single family residential structures during
re-roofing.  For site-built single family residential
structures the fasteners and spacing required in Table 201.1 are deemed to
comply with the requirements of Section 511.5, 
201.2  Roof
sheathing fastening for site-built single family residential structures prior
to re-roofing.  When a home
inspection completed for a real estate transaction reveals that the roof
decking attachment does not meet the fastener requirements of Table 201.1, and
when this roof will not be re-roofed at the time of the transaction, an AFG-01
approved adhesive shall be applied in a ¼” bead to the 90-degree joint between
the underside of the roof decking and the supporting roof framing to strengthen
this connection.
FRSA Comment:
201.2  Roof
secondary water barrier for site-built single family residential structures.  A secondary water barrier shall be installed
using one of the following methods when roofing replacement when
reproofing, and all materials used must
meet the requirements of FBC’s product approval system for wind driven rain and
wind uplift resistance.  
a)         All joints in roof
sheathing or decking shall be covered with a minimum 4 in. wide strip of adhered approved membrane self-adhering
polymer modified bitumen tape applied directly to the sheathing or
decking.  The deck and self adhering
polymer modified bitumen tape shall be covered with one of the underlayment
systems approved for the particular roof covering to be applied to the roof.
b)         The entire roof deck
shall be covered with an approved adhered
membrane self-adhering polymer modified bitumen cap sheet.  No additional underlayment shall be required
on top of this cap sheet for new installations.
c) The entire roof deck shall
be covered with a mechanically attached approved membrane.
d) All joints in the roof
sheathing shall be sealed with an approved sealant.
e)  All joints in the roof sheathing shall be
sealed with an approved sealant; the entire roof shall then be covered with an
approved coating.
EXCEPTIONS:
An asphalt impregnated 30# felt underlayment installed with nails and
tin-tabs as required for the HVHZ and covered with either an approved
self-adhering polymer modified bitumen cap sheet or an approved cap sheet
applied using an approved hot-mop application shall be deemed to meet the
requirements for the secondary water barrier.
Bill Dumbaugh’s
Comment:
201.2  Secondary water barrier for site built single
family residential structures.
A secondary water barrier shall be installed
using one of the following methods when roofing replacement when reproofing.  
EXCEPTIONS:
1. In lieu of 1 and 2 above,
buildings and structures located in HVHZ with nailable decks shall be installed
in accordance with section 1518, 
and  1519, which shall be deemed
to meet the requirements of  a secondary
water barrier 
1   A asphalt impregnated 30# felt underlayment
installed with nails and tin-tabs as required for the HVHZ and covered with
either an approved self-adhering polymer modified bitumen cap sheet or an
approved cap sheet applied using an approved hot-mop application shall be
deemed to meet the requirements for the secondary water barrier.
2.  A roof deck that is
sufficiently fastened as prescribed in Section 201.1 and provided with a
secondary water barrier as outlined above shall be deemed to meet the
requirements of this section.
Chris Schulte’s
comments.

Ray Burroughs
Comment:
Table 201.3, last column headered “overhangs”, is this
for all overhang projections, obviously a 12 inch overhang has less uplift than
a 24 inch overhang.
General Comments:
Robert Bullard’s
Comments:
Our sister firm, Preservation Possibilities, Inc., uses
a custom latex elastomeric coating material manufactured in the USA to anchor
existing asphalt shingle roofs against being stripped off by high winds.  The attached annotated photo shows two side
by side comparisons:  the less dense
coating provides moderate wind-stripping resistance, the more dense will
restrain the roofing to the extent that the original nails will hold the
shingles themselves to the roof deck with no wind-peeling whatsoever for the
life of the coating.
The coating is spray-applied to weathered roofs
(shingles over five years old), with spray-jet challenging 100 per cent of the
down slope flaps of the shingles (except those at the extreme edge of the
roof), so that a significant amount of material extends up under the leading
edge of the shingles to act as an adhesive. 
The less dense coating is a single layer spray application which is
back-rolled with minimal membrane development over the leading edge.  This application is intended for moderate enhancement
of wind up-lift resistance of shingles; its main benefit is that by applying
the special mildew-resistant white coating, there is at least a twenty per cent
reduction in the energy bill of a typical single-story centrally-cooled 
As the coating weathers free of leaf deposition, the
efficiency of the coating declines to about one-half of its original benefit at
ten years, at which point a thin 50 square feet per gallon top coat can be
applied to restore the energy efficiency.
The more dense application is achieved by applying a
second coating to create and intact membrane over the leading edge of the
shingles.  If the original roofing was
properly nailed (e. g., at least 6, 6d or larger per architectural shingle
profile), a shingle roof with this coating is virtually unstrippable by wind,
except for, perhaps, the first row of shingles at the edge strip. (With respect
to anchoring the edge, at a single project site, we have have achieved robust
anchorage by pneumatically-driven pairs of “X” pattern monel staples through
the edge flaps and the metal drip edge under the flap in the perimeter of the
roof overhang; there were three clusters (pairs) per architectural shingle. At
this particular site (oceanfront) we have yet to coat because the shingles are
still too “fresh” with asphalt solvents which can potentially impair the bond
and chemical properties of the coating material.)
Present installed cost for the two-coat system is no
more than the cost of the least expensive asphalt shingle replacement roof, a
product which will not have nearly the energy efficiency or wind resistance of
the two-coat roof.
 Present installed
cost for the two-coat system is no more than the cost of the least expensive
asphalt shingle replacement roof, a product which will not have nearly the
energy efficiency or wind resistance of the two-coat roof.
This coating system is a win-win for aged asphalt shingle roofs which do not have advanced deterioration problems (leaks, corrosion of flashings, rotten wood, etc.). (If there are leaks without structural consequences, these can usually be cured with the two-coat system, or, if around roof penetrations, such as vents, skylights, chimneys, etc. with multiple stripe coats during the original coating or subsequently.) With a top coating every ten years at about half the cost of the original two-coat roof, such a roofing system lasts forever. It should be part of the arsenal of the My Florida Safe Home concept.

