FLORIDA
BUILDING COMMISSION
STRUCTURAL
TAC
CONCURRENT
WITH
SPECIAL OCCUPANCY TAC
Minutes
WEBINAR / TELECONFERENCE
Thursday, January 24, 2013, 
10:00am – 11:35am
 
| MEETING OBJECTIVES | ||
| Ø To review and provide
  recommendations on Declaratory Statements and other business on behalf of the
  Commission.  | ||
|  MEMBERS | ||
| ØMembers present: James Schock – Chair, CW Macomber, Steve Strawn,
  Craig Parrino, Bill Dumbaugh
  alternate for Daniel Lavrich, Do Kim, Jack
  Glenn, Jaime Gascon, Warner Chang, Harry
  “Rusty” Carroll | ||
| 10:00
  AM | A) | Called to Order a quorum was
  achieved with 10 members present.   The
  meeting was held concurrently with the Special Occupancy TAC.  The Special Occupancy TAC achieved a quorum
  too.    The Agenda and minutes were
  both approved as submitted. | 
|   | B) | Reviewed and provide the
  following recommendations on Declaratory Statements and other business on
  behalf of the Commission.  1.                
  DS 2012-081 – By Joseph Scofield of Advanced Manufacturing & Power Systems
  Inc.  1.      A Client intends to install an electrical
  generator set in an enclosure to provide emergency backup power to a hospital
  in the event of a loss of utility power.  There will be no other
  debris impact protection aside from the generator enclosure.  According to FBC 419.4.2.9.6 “The
  emergency generator(s) shall be air or self-contained liquid cooled and it
  and other essential electrical equipment shall be installed in a protected
  area(s) designed and constructed to meet the structural requirements of the
  code and debris impact requirements of Sections 1626.2 through 1626.4”. a.       Is the generator enclosure required to be
  tested and approved per Section 1626 of the 2010 Florida Building Code and
  bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
  of Acceptance approval?   Answer: As per Section
  419.4.2.9.6 of the 2010 FBC, Building “the Code”, the generator enclosure in
  question must be constructed to meet the structural requirements of the Code
  and the debris impact requirements of Sections 1626.2 through 1626.4 as
  applicable.  Further, in order to demonstrate compliance with the
  debris impact requirements of the Code, the generator enclosure or its
  components must be either tested to TAS 201, 202, and 203 in accordance with
  the requirements of Sections 1626.2 and 1626.3 as applicable or
  designed/constructed to meet the deemed to comply standards
  of Section 1626.4 as applicable. Product approval of the enclosure in question
  as meeting the debris impact requirements of the Code is subject to the
  review and discretion of the authority having jurisdiction.   2.      A Client intends to install an electrical
  generator set in an enclosure to provide emergency backup power to a Nursing
  Home in the event of a loss of utility power.  There will be no
  other debris impact protection aside from the generator enclosure.  According to FBC 420.4.2.9.6 “The
  emergency generator(s) shall be air or self-contained liquid cooled and it
  and other essential electrical equipment shall be installed in a protected
  area(s) designed and constructed to meet the structural requirements of the
  code and debris impact requirements of Sections 1626.2 through 1626.4”. a.       Is the generator enclosure required to be
  tested and approved per Section 1626 of the 2010 Florida Building Code and
  bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
  of Acceptance approval?   Answer: As per Section
  420.4.2.9.6 of the 2010 FBC, Building “the Code”, the generator enclosure in
  question must be constructed to meet the structural requirements of the Code
  and the debris impact requirements of Sections 1626.2 through 1626.4 as
  applicable.  Further, in order to demonstrate compliance with the
  debris impact requirements of the Code, the generator enclosure or its
  components must be either tested to TAS 201, 202, and 203 in accordance with
  the requirements of Sections 1626.2 and 1626.3 as applicable or
  designed/constructed to meet the deemed to comply standards
  of Section 1626.4 as applicable. Product approval of the enclosure in
  question as meeting the debris impact requirements of the Code is subject to
  the review and discretion of the authority having jurisdiction.   3.      A Client intends to install an electrical
  generator set in an enclosure to provide emergency backup power to an
  Enhanced Hurricane Protection Area (EHPA) as part of an Educational Facility
  Public Shelter in the event of a loss of utility power.  There will
  be no other debris impact protection aside from the generator
  enclosure.  According to FBC 423.25.5 “When
  generators are installed, the facility housing the generator, permanent or
  portable, shall be an enclosed area designed to protect the generators from
  wind and missile impact. Air intakes and exhausts shall be designed and
  installed to meet the wind load and missile impact criteria. Generators
  hardened by the manufacturer to withstand the area’s design wind and missile
  impact criteria shall be exempt from the enclosed area criteria requirement.” a.       Is the generator enclosure required to be
  tested and approved per Section 1626 of the 2010 Florida Building Code and
  bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
  of Acceptance approval?   Answer:    According to Section 423.25.5 of the
  2010 Florida Building Code, Building (the Code); the generator enclosure or
  its components is required to be designed to protect the generator from wind
  and missile impact and thus the generator enclosure or its components must be
  tested and approved as meeting the impact requirements of Section 423.25.4.1
  of the Code.     4.      A Client intends to install an electrical
  generator set in an enclosure to a commercial facility located in a High
  Velocity Hurricane Zone (HVHZ) to provide emergency backup power in the event
  of a loss of utility power.  The generator Set and enclosure will
  be installed on the roof of the facility.  There will be no other
  debris impact protection aside from the generator enclosure.    According to FBC 1601.1 “The provisions
  of this chapter shall govern the structural design of buildings, structures
  and portions thereof regulated by this code.  a.       Is the generator enclosure required to be
  tested and approved per Section 1626 of the 2010 Florida Building Code and
  bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
  of Acceptance approval?   Answer:    Yes.
  The enclosure in question is part of a building which must be constructed to
  meet the structural requirements of the Code and the debris impact
  requirements of Sections 1626.2 through 1626.4 as applicable.  Further,
  in order to demonstrate compliance with the debris impact requirements of the
  Code, the generator enclosure or its components must be either tested to TAS
  201, 202, and 203 in accordance with the requirements of Sections 1626.2 and
  1626.3 as applicable or designed/constructed to meet the deemed to comply standards of Section 1626.4 as applicable.
  Product approval of the enclosure in question as meeting the debris impact
  requirements of the Code is subject to the review and discretion of the
  authority having jurisdiction.   5.      A Client intends to install an electrical
  generator set in an enclosure to a commercial facility located in a High
  Velocity Hurricane Zone (HVHZ) to provide emergency backup power in the event
  of a loss of utility power.  The generator Set and enclosure will
  be installed on the ground floor of the facility.  There will be no
  other debris impact protection aside from the generator enclosure.    According to FBC 1601.1 “The provisions
  of this chapter shall govern the structural design of buildings, structures
  and portions thereof regulated by this code.  a.       Is the generator enclosure required to be
  tested and approved per Section 1626 of the 2010 Florida Building Code and
  bear either appropriate Florida Product Approval numbers or Miami-Dade Notice
  of Acceptance approval?   Answer:    Yes.
  The enclosure in question is a building which must be constructed to meet the
  structural requirements of the Code and the debris impact requirements of
  Sections 1626.2 through 1626.4 as applicable.  Further, in order to
  demonstrate compliance with the debris impact requirements of the Code, the
  generator enclosure or its components must be either tested to TAS 201, 202,
  and 203 in accordance with the requirements of Sections 1626.2 and 1626.3 as
  applicable or designed/constructed to meet the deemed to comply standards of Section 1626.4 as applicable.
  Product approval of the enclosure in question as meeting the debris impact
  requirements of the Code is subject to the review and discretion of the
  authority having jurisdiction. 
 Question 1:  Does the
  term “protection of openings” mean the same as the term “opening protection”,
  as found in the text of the referenced section, and specific to “protection
  from windborne debris”?       Answer: Yes, the term “protection of openings” is analogous to the term
  “opening protection” as referenced in Section 1609.1.2 of the 2010 Florida
  Building Code, Building and specific to “protection from windborne debris.” Question 2:  Is the
  non-glazed door required to comply with Section 1609.1.2?       Answer: No, Section 1609.1.2 is specific to glazed products. Question 3: If the
  non-glazed door is not required to comply with Section 1609.1.2, but it
  complies with the wind load requirements of the code, would the door also
  comply with the code as “opening protection”? Answer: A non-glazed door is not required to be
  protected in accordance with Section 1609.1.2 in a
  non-HVHZ zone Question 4:  Would the
  state-approved, glazed garage door rated for non-HVHZ impact resistance be
  acceptable for the job (which is outside the HVHZ) without an NOA?       Answer: Yes, if used as per the limits of use of the Product
  Approval. 
 RE: Project #1) In the scope of the work plan review for
  permitting the process of stabilizing an interior concrete slab, on grade,
  for a 2000 sq. ft. existing dwelling unit that was built in 2001, the
  application consists of injecting pressurized structural polyurethane resin
  through the slab, on grade, by using core drilled holes in which the
  polyurethane resin expands to lift/stabilize the concrete slab. This process
  has no control of the path of flow for the polyurethane resin in which direct
  contact with the slab on grade concrete is possible.  Question –
  Does  injecting this pressurized structural polyurethane resin for
  soil stabilization thru the slab on grade for existing dwellings, with
  possible direct contact with the concrete slab on grade, constitute a
  violation of 2010 FBC-R Section 318.5? Answer: No.  The application of Section R318.5 of the
  FBC, Residential is limited in scope to new construction. RE:  Project
  #2)  In the
  scope of the work plan review for permitting the process of stabilizing an
  exterior foundation/footer for a 1450 sq. ft. existing dwelling unit that was
  built in 1985, the application consists of injecting structural polyurethane
  resin in the ground outside of the existing dwelling unit to provide
  structural support for the foundation /footer.  This process has no
  control of the path of flow for the polyurethane resin in which direct
  contact with the foundation/footer is possible. Question - Does injecting this structural polyurethane
  resin into the ground outside the existing dwelling unit with possible direct
  contact with the foundation/footer constitute a violation of 2010FBC-R
  318.5?  Answer:  No. The provisions of Section R318.5 of the FBC,
  Residential do not apply to the projects in question.   4.           
  DS 2012-097 – By Robert W. Moody,
  Jr. of Uretek Holdings, Inc.  Question No. 1 Is the installation of
  a rigid structural geotechnical polymer into the ground as a method of soil stabilization
  for an existing building prohibited by the 2010 Florida Building Code, Residential, Chapter
  3, Code Section R318.5?   Answer:  No.  The provisions of Section R318.5 of
  the FBC, Residential do not apply to the projects in question. Question No. 2 Are soil stabilization
  techniques as discussed herein regulated by 2010 Florida Building Code – Residential and/or Existing Building? Answer: The applications of the soil stabilization techniques in
  question fall within the technical scope of the 2010 Florida Building Code,
  Existing Building and not the Florida Building Code, Residential. | 
|   | D) | No Public Comment | 
|   | E) | Adjourned at 11:35 am | 
STAFF CONTACTS: Joe Bigelow, joe.bigelow@dbpr.state.fl.us, (850) 922-0359; Mo Madani, Manager
Note: This document is available to any person requiring materials in
alternate format upon request. Contact the Department of Business and
Professional Regulation, 2555 Shumard Oak Boulevard,
Tallahassee, Florida 32399-2100 or call 850-487-1824.